What exact power does the S23e U2H take? 3-phase only?
AsicProfit SupportAsicProfit · 2026年10月26日
Yes, three-phase only. Bitmain gives an AC input range of 342 to 528 V, a rated range of 380 to 480 V at 50 to 60 Hz, a maximum input current of 20 A and an LP34 power port. Typical draw is 8650 W at a 35 C coolant inlet. Wrong input voltage can damage the server, so have the electrical side done by a qualified electrician.
Petr S. · 2026年10月16日
What coolant flow, temperature and pH does the S23e Hyd need?
AsicProfit SupportAsicProfit · 2026年10月17日
Bitmain lists inlet coolant at 20 to 50 C (35 C typical), flow of 16 to 20 L/min, and pressure up to 3.5 bar. You can use antifreeze, deionized water or pure water, with pH targets of 7.0 to 9.0 for antifreeze, 8.5 to 9.5 for deionized water and 6.5 to 7.5 for pure water. The pipe connector is UQD08. Keep the loop clean and filtered.
Oleh B. · 2026年9月29日
How long is the warranty on the S23e Hyd 2U compared to air-cooled Antminers?
AsicProfit SupportAsicProfit · 2026年9月30日
Bitmain lists a 365-day warranty from the shipping date for the S23e U2H, longer than the 180 days it gives on several air-cooled models such as the KS7. The warranty applies to the original buyer who purchased directly from Bitmain. If you buy through a reseller, the reseller handles warranty, so get their terms in writing.
Anna S. · 2026年9月19日
Will a 2U S23e fit in a normal server rack?
AsicProfit SupportAsicProfit · 2026年9月20日
It is a 2U rack unit at 600 x 482.6 x 86 mm without packaging, so it fits standard 19 inch rack width, but you need enough depth for the chassis plus coolant connections and the power cable. Each unit weighs roughly 28 to 31 kg, so check your rack's load rating and use proper rails. Bitmain also sells racks and containers designed for these 2U hydro units.
Gabor N. · 2026年9月16日
Can I run an S23e Hyd 2U at home or is it strictly for data centers?
AsicProfit SupportAsicProfit · 2026年9月17日
It is built for racks and liquid-cooling infrastructure. Bitmain specifies three-phase power with a rated range of 380 to 480 V, about 8650 W per unit, and a coolant loop with 16 to 20 L/min of flow. Bitmain points to its container and dry-cooling tower manual for coolant handling. A home build is possible only with three-phase supply, a pump, heat exchanger and plumbing, so most buyers host it.
Jake T. · 2026年9月15日
Anything special about storing or shipping an S23e Hyd between sites?
AsicProfit SupportAsicProfit · 2026年9月16日
Yes. Bitmain warns that the server must be stored completely dry, with no coolant or water left inside, because residual liquid can cause corrosion, short circuits and permanent damage. Drain and dry the unit before storage or transport. Bitmain lists a storage temperature of -40 to 85 C and operating humidity of 10 to 90 percent, non-condensing.